全站搜索
医院中心供氧系统氧气站三种方式分别是液态氧储罐、医用制氧机、氧气瓶汇流排。
中大型医院一般首选液态氧储罐,医用制氧机次之。规模较大的医养结合机构可根据前期投入预算、环境条件、后期对氧气用量及便捷度、经济性等情况选择液态氧罐或制氧机,液态氧罐需要放置在主体大楼以外,对周边环境有间距要求。医院中心供氧总床位100以下的小型医院和乡镇卫生院考虑前期成本投入,一般选用氧气瓶汇流排的方式,充灌氧气不方便的地区也会选用3立方-5立方(每小时产氧量)的小型医用制氧机。可根据不同规模及使用场景技术要求选购医用中心供氧设设备。
根据医用气体工程技术规范GB50751-2012标准规定,医用气体工程正负压管道可选用脱脂紫铜管和304脱脂不锈钢管,医院中心供氧系统管道属于正压系统管道。医用中心供氧管道设备主要包含减压和截止阀门、多幢病房楼独立设置多条氧气主管道时,需要在氧气站处设立分汽缸;每个病区或者楼层设立二级稳压箱(二级减压箱)与流量计,值班室与护理站应设立氧气压力观测与声光报警装置。
Coronaviruses are a large family of viruses. Some cause illness in people, and others, such as canine and feline coronaviruses, only infect animals. Rarely, animal coronaviruses that infect animals have emerged to infect people and can spread between people
Coronaviruses are a large family of viruses. Some cause illness in people, and others, such as canine and feline coronaviruses, only infect animals. Rarely, animal coronaviruses that infect animals have emerged to infect people and can spread between people
What is community spread?
Coronaviruses are a large family of viruses. Some cause illness in people, and others, such as canine and feline coronaviruses, only infect animals. Rarely, animal coronaviruses that infect animals have emerged to infect people and can spread between people
GB50751-2012医用气体工程技术规范第4.6.4医用液氧贮罐与建筑物、构构筑物的防火间距规定:医疗卫生机构液氧贮罐处的实体围墙高度不应低于2.5m;当围墙外为道路或开阔地日时,贮罐与实体围墙的间距不应小于1m;围墙外为建筑物、构筑物时,贮罐与实体围墙的间距不应小…
GB 50751 – 2012医用气体工程技术规范,可作为医院气体工程建设重要的技术标准参考依据,包含医用中心供氧系统、医用负压吸引系统、医用压缩空气系统及相关医用医用气体工程施工技术标准。
医用气体管道系统工程安装规范1、敷设压缩医用气体管道的场所,其环境温度应始终高于管道内气体的露点温度5℃以上,因寒冷气候可能使医用气体析出凝结水的管道部分应采取保温措施。医用真空管道坡度不得小于0.002。2、医用氧气、氮气、二氧化碳、氧化亚氮及其混合气体…
医疗卫生机构应根据自身的需求,在必要时设置医用气体系统计量仪表,可以用于医用中心供氧系统、医用压缩空气系统、医用混合气体系统等,可以选择安装在每个病区或者病房楼层作为区域氧气和各类医气的流量统计。
氧气源由好多种,最常见的有制氧机制氧、液氧贮罐、瓶装氧等。制氧机制氧因其经济性、安全性、稳定性来说是目前医院常选择的制氧方式,液氧贮罐一般是大型医院的首选,瓶装氧一般作为医院的备用氧使用,由于不同的氧气源有着不同的要求和制氧贮氧的不同性,因此在选…
医院,因其场所的特殊性,是净化使用最多的场所,也是净化要求等级最高的场所,因此净化质量要求的严格与否直接影响着患者的健康安全以及关系着医疗质量的提升。医院的净化系统涉及面广泛,工程质量要求高,那么具体净化要求工程包含哪些呢,下面来看一下。